Ideal Heating · Heat-pump or fixed-AC model
Logic Air 10kW
Ideal Logic Air 10kW, product code AH750667, is the largest current model in the single-phase R32 monobloc range.
Specifications
| Specification | Value |
|---|---|
| Type | air-source, air-to-water monobloc, inverter-driven |
| Supply phases | single |
| Rated output (kW) | 10.0 at 7°C outdoor air with 35°C or 55°C water in Ideal Rev D |
| Rated-output conditions | the live HTML table separately shows 10.3 kW; match the exact current document and serial |
| SCOP (seasonal coefficient of performance) at 35°C | 5.19 in Ideal Rev D; 4.57 in the MCS (Microgeneration Certification Scheme) Product Directory on 23 July 2026 |
| SCOP at 55°C | 3.73 in Ideal Rev D; 3.65 in the MCS Product Directory on 23 July 2026 |
| Maximum flow temperature (°C) | 60 |
| Minimum operating temperature (°C) | -20 |
| Refrigerant | R32, 1.47 kg |
| Sound power (dB) | 55 dB(A), tested to EN 12102-1 |
| MCS certified | yes, MCS reference KIWA 00027/022 HP; current to 25 August 2027 at review date |
| Warranty (years) | up to 7 under current standard homeowner conditions; optional paid extension page gives a maximum of 10 |
| Dimensions, height × width × depth (mm) | 1008 × 1095 × 518 |
| Weight (kg) | 110 |
Logic Air 10kW is product code AH750667 and the largest capacity in the current Logic Air range. It uses a single-phase supply and shares the larger outdoor casing with the 8 kW model.
Named and condition-specific output
The March 2026 Rev D sheet gives 10.0 kW at 7°C outdoor air with either 35°C or 55°C water. The live HTML product table separately gives 10.3 kW at those points. The exact current document and serial-specific installation information therefore need to match the unit.
Neither figure states output at the property’s design outdoor temperature. Ideal publishes separate capacity rows across colder outdoor conditions and higher flow temperatures. That output map is compared with the building heat loss and emitter design.
Rev D gives SCOP (seasonal coefficient of performance) values of 5.19 at 35°C and 3.73 at 55°C. The MCS Product Directory record current on 23 July 2026 instead gave 4.57 and 3.65. The two datasets are retained separately.
Outdoor unit and water circuit
The R32 factory charge is 1.47 kg. Published dimensions are 1,008 mm high, 1,095 mm wide and 518 mm deep, and the unit weighs 110 kg. Ideal’s minimum hydronic flow is 14.5 litres per minute.
The operating information gives a -20°C minimum outdoor temperature and 60°C maximum flow temperature. Available heat at a particular combination comes from the operating map, not from combining those two limits with the 10 kW name.
Published sound power is 55 dB(A). The property’s acoustic assessment converts source data into a receptor-specific result using distance, direction, reflections and barriers.
Certification and warranty
KIWA 00027/022 HP was current through 25 August 2027 at the review date. Ideal’s standard homeowner page states up to seven years of parts-and-labour cover with registration within 30 days and annual servicing, subject to terms. Its optional paid Logic Air extension has a stated ten-year maximum.
Related entries
Manufacturer and reference sources
Brand
Reference type
Heat-pump or fixed-AC model
Last reviewed
23 Jul 2026
Current status
Current in the manufacturer's UK range.