Samsung · Heat-pump or fixed-AC model
EHS Mono HT Quiet
Samsung EHS Mono HT Quiet is an R32 monobloc outdoor-unit range in 8, 12 and 14 kW classes with a 70°C leaving-water limit.
Specifications
| Specification | Value |
|---|---|
| Type | monobloc air-source, air-to-water heat pump |
| Maximum flow temperature (°C) | 70 |
| Minimum operating temperature (°C) | -30 for the 8 kW outdoor unit |
| Refrigerant | R32 in the outdoor unit |
| Sound power (dB) | 56 for the 8 kW outdoor unit |
| MCS certified | yes; exact combinations containing these six outdoor-unit codes were present on 23 July 2026 |
| Product codes | AE080BXYDEG/EU, AE080BXYDGG/EU, AE120BXYDEG/EU, AE120BXYDGG/EU, AE140BXYDEG/EU and AE140BXYDGG/EU |
| Capacity classes (kW) | 8, 12 and 14 |
| Supply phases | DEG single-phase; DGG three-phase |
| Sound pressure db | 42 for the 8 kW outdoor unit; as low as 35 in four-step quiet mode |
EHS Mono HT Quiet is Samsung’s R32 high-temperature monobloc range. Its outdoor codes use AE080BXY, AE120BXY and AE140BXY prefixes for the 8, 12 and 14 kW capacity classes.
Output and electrical forms
This entry maps the six current outdoor-unit codes:
| Capacity class | Single-phase outdoor unit | Three-phase outdoor unit |
|---|---|---|
| 8 kW | AE080BXYDEG/EU |
AE080BXYDGG/EU |
| 12 kW | AE120BXYDEG/EU |
AE120BXYDGG/EU |
| 14 kW | AE140BXYDEG/EU |
AE140BXYDGG/EU |
DEG identifies the 220–240 V single-phase version and DGG identifies the
380–415 V three-phase version. Leaving-water temperature reaches 70°C, while
the 8 kW model operates in heating mode down to -30°C.
These limits do not establish the useful output or efficiency at a project’s design point. The exact performance table is needed at the design outdoor temperature and selected heating-water temperature.
Normal and quiet-mode sound figures
The 8 kW outdoor unit has sound figures of 42 dB(A) pressure and 56 dB(A) power. Its four-step quiet mode can reduce sound pressure to 35 dB(A). Those figures use different operating conditions and should not be treated as interchangeable.
The planning or MCS noise calculation uses the declared sound power for the exact outdoor unit, its position and nearby reflective surfaces. A quiet-mode figure is relevant only where the commissioned control settings and design assumptions match it.
System and certification records
Mono HT Quiet keeps R32 in the outdoor unit and connects hydraulically to a Samsung control kit or indoor package. This entry does not prescribe a control-kit, ClimateHub or cylinder pairing.
Exact combinations containing all six outdoor-unit codes were present in the MCS Product Directory on 23 July 2026. Several control-module and ClimateHub pairings exist, so the exact complete combination must be checked against the current MCS record and Samsung compatibility material.
Related entries
Manufacturer and reference sources
Brand
Reference type
Heat-pump or fixed-AC model
Last reviewed
31 Jul 2026
Current status
Current in the manufacturer's UK range.